Design and Optimization of Insulation Structure of Three-phase Tri-post Insulator in 252 kV Compact GIL
|更新时间:2025-12-08
|
Design and Optimization of Insulation Structure of Three-phase Tri-post Insulator in 252 kV Compact GIL
Vol. 46, Issue 6, Pages: 2030-2039(2020)
作者机构:
1. 西安交通大学电力设备电气绝缘国家重点实验室
2. 中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2020,
Published:2020
稿件说明:
移动端阅览
WU Zehua, TIAN Huidong, JIN Shoufeng, et al. Design and Optimization of Insulation Structure of Three-phase Tri-post Insulator in 252 kV Compact GIL[J]. 2020, 46(6): 2030-2039.
DOI:
WU Zehua, TIAN Huidong, JIN Shoufeng, et al. Design and Optimization of Insulation Structure of Three-phase Tri-post Insulator in 252 kV Compact GIL[J]. 2020, 46(6): 2030-2039.DOI:
Design and Optimization of Insulation Structure of Three-phase Tri-post Insulator in 252 kV Compact GIL
When GIL changes from single-phase operation to three-phase
the insulation structure of post insulator with sliding design will become more complex
and the difficulty in design will be significantly increased. In order to improve the operation reliability of 252 kV compact GIL
the electric field distribution characteristics of three-phase tri-post insulator were simulated and analyzed by using the finite element method. The design indexes of insulation structure were extracted and transformed into dimensionless index f. The variation law of f with typical structure parameters was discussed and the influence degree of typical structural parameters on design indexes was obtained by variation coefficient method. On this basis
this paper presented the optimization design sequence and the improvement scheme. In addition
the method of improving the capacitance distribution between electrodes to the surface field distribution of metal parts uniform was analyzed. The results show that the total and tangential field strength on insulator surface of the improved scheme are reduced by 6.9% and 11.1%
respectively. While on metal insert surface
the total filed strength is reduced by 30.1%. The usage of improved scheme ensures the design indexes to meet the requirements of the critical value
which has an important significance and reference for the design of three-phase tri-post insulator in 252 kV compact GIL.