Charge Accumulation and Electric Field Transition Characteristics of Basin Insulator Under DC Voltage
|更新时间:2025-12-08
|
Charge Accumulation and Electric Field Transition Characteristics of Basin Insulator Under DC Voltage
Vol. 46, Issue 6, Pages: 1978-1985(2020)
作者机构:
1. 国网安徽省电力有限公司电力科学研究院
2. 国网安徽省电力有限公司
3. 合肥工业大学电气与自动化工程学院
4. 西安交通大学电力设备电气绝缘国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2020,
Published:2020
稿件说明:
移动端阅览
YANG Wei, ZHU Taiyun, TIAN Yu, et al. Charge Accumulation and Electric Field Transition Characteristics of Basin Insulator Under DC Voltage[J]. 2020, 46(6): 1978-1985.
DOI:
YANG Wei, ZHU Taiyun, TIAN Yu, et al. Charge Accumulation and Electric Field Transition Characteristics of Basin Insulator Under DC Voltage[J]. 2020, 46(6): 1978-1985.DOI:
Charge Accumulation and Electric Field Transition Characteristics of Basin Insulator Under DC Voltage
摘要
直流电压作用时
气–固绝缘系统电场由容性分布逐渐向阻性分布过渡
该过程伴随着电荷的积聚与消散
可能会引起闪络电压降低
但其变化规律仍不够明确。综合考虑了固体侧体电荷电导、气体侧正负离子电导以及界面电荷电导
建立了气–固绝缘系统电荷积聚模型
通过支柱绝缘子模型表面电位分布的测量与仿真
实现了电荷积聚模型的验证。利用该模型计算分析了直流电压下盆式绝缘子在电场过渡过程中的电荷积聚规律
研究了体积电导率对电荷积聚的影响规律。结果表明:电场过渡过程中
盆体凸面主要积聚同极性电荷
其高压侧附近场强降低约9.4%
低压侧附近场强增大约23.5%;盆体凹面大部分区域主要积聚异极性电荷
场强增大约5.5%;当体积电导率在10
-14
~10
-17
S/m之间时
盆体凸面积聚同极性电荷
盆体凹面主要积聚异极性电荷
随着体积电导率进一步降低
盆体表面电荷积聚机制逐渐转为由气体侧电导主导
电场畸变进一步加剧。该研究可为直流盆式绝缘子的绝缘设计提供计算分析依据。
Abstract
The electric field of gas-solid insulation system will gradually transit from capacitive distribution to resistive distribution under DC voltage. This process is accompanied by the accumulation and dissipation of charges
which may cause the decrease of flashover voltage
but the regularity is still not clear enough. Consequently
the volume charge conductance in solid
ions conductance in gas and interface charge conductance were taken into consideration
so that a charge accumulation model for gas-solid insulation system was established. And the correctness of the model was verified by measuring and simulating the surface potential distribution of a post insulator sample. Moreover
the charge accumulation o
n the surface of basin insulator during the electric field transition process under DC voltage was computed and analyzed. The influence of volume conductivity on charge accumulation characteristics was investigated. The results show that
in the process of electric field transition
the convex surface of the basin mainly accumulates homopolar charges. The electric field intensity near the high-voltage side decreases by 9.4% and the electric field intensity near the low-voltage side increases by 23.5%. The heteropolar charges mainly accumulate in most areas of concave surface and the electric field intensity increases by 5.5%. When the volume conductivity is between 10
-14
S/m and 10
-17
S/m
the convex surface of the basin insulator accumulates homopolar charges
while the concave surface mainly accumulates heteropolar charges. With the further decrease of volume conductivity
the mechanism of charge accumulation on the surface of basin insulator gradually turns to be dominated by gas-side conductivity. And the electric field distortion on the surface of basin insulator is further aggravated. The research in this paper can provide a calculation and analysis reference for the insulation design of DC basin insulators.