Monitor and Alarm Technology of Wildfire Occurrences in Transmission Lines Corridors Based on Himawari-8 Geostationary Meteorological Satellite
|更新时间:2025-12-08
|
Monitor and Alarm Technology of Wildfire Occurrences in Transmission Lines Corridors Based on Himawari-8 Geostationary Meteorological Satellite
Vol. 46, Issue 7, Pages: 2561-2569(2020)
作者机构:
1. 长沙理工大学电气与信息工程学院清洁能源与智能电网2011协同创新中心
2. 国家卫星气象中心
3. 广东电网有限责任公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 July 2020,
Published:2020
稿件说明:
移动端阅览
ZHOU You, SUI Sanyi, CHEN Jie, et al. Monitor and Alarm Technology of Wildfire Occurrences in Transmission Lines Corridors Based on Himawari-8 Geostationary Meteorological Satellite[J]. 2020, 46(7): 2561-2569.
DOI:
ZHOU You, SUI Sanyi, CHEN Jie, et al. Monitor and Alarm Technology of Wildfire Occurrences in Transmission Lines Corridors Based on Himawari-8 Geostationary Meteorological Satellite[J]. 2020, 46(7): 2561-2569.DOI:
Monitor and Alarm Technology of Wildfire Occurrences in Transmission Lines Corridors Based on Himawari-8 Geostationary Meteorological Satellite
Limited by the time intervals of passing territory of polar orbit satellites
it is impossible to monitor wildfire occurrences in power transmission line corridors uninterruptedly by using polar orbit satellites. In this paper
an alarming technique based on Himawari-8 geostationary meteorological satellite is proposed to monitor wildfire occurrences in power transmission lines corridors. In order to ensure the accuracy and universality of the recognition algorithm
an adaptive dynamic method
which considers the influences of the solar elevation angle
the non-vegetation pixel
and the cloud pixel
is proposed to determine the bright temperature thresholds of different regions. In addition
the information of power transmission lines as well as their fire-risk levels are pre-stored in grids to improve the efficiency of fire-point alarming system. Once a monitored wildfire locates in these girds
the information of the power tower and its fire-risk level are then output to the local maintenance staffs. This wildfire alarming technique has been applied in a provincial power grid in the southern of China. It realizes 24 h uninterrupted monitoring and alarm of wildfire occurrences in power transmission line corridors. And all the wildfires occurrences have been disposed to avoid wildfire induced transmission-line trip failures during the Tomb-Sweeping Days in 2017—2019.