Influential Factors of Voltage Sharing for Series Multi-break Fast Mechanical Switch of ±500 kV Hybrid HVDC Circuit Breaker
|更新时间:2025-12-08
|
Influential Factors of Voltage Sharing for Series Multi-break Fast Mechanical Switch of ±500 kV Hybrid HVDC Circuit Breaker
Vol. 46, Issue 8, Pages: 2706-2713(2020)
作者机构:
武汉大学电气与自动化学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2020,
Published:2020
稿件说明:
移动端阅览
QUAN Wanlin, HUANG Daochun, WANG Xuezong, et al. Influential Factors of Voltage Sharing for Series Multi-break Fast Mechanical Switch of ±500 kV Hybrid HVDC Circuit Breaker[J]. 2020, 46(8): 2706-2713.
DOI:
QUAN Wanlin, HUANG Daochun, WANG Xuezong, et al. Influential Factors of Voltage Sharing for Series Multi-break Fast Mechanical Switch of ±500 kV Hybrid HVDC Circuit Breaker[J]. 2020, 46(8): 2706-2713.DOI:
Influential Factors of Voltage Sharing for Series Multi-break Fast Mechanical Switch of ±500 kV Hybrid HVDC Circuit Breaker
HVDC circuit breakers are the key protection equipment for HVDC power grids. In the main branch of hybrid HVDC circuit breaker
the fast mechanical switch adopts the form of series multi-break to ensure the requirement of operating rapidity. Choosing appropriate voltage-sharing component parameters is an important guarantee for the fast mechanical switch to meet the static and dynamic voltage withstand property. But it may be affected by many factors in actual operation
and the concerned research results are few. Taking the series six-break 550 kV fast mechanical switch as an example
which makes up the ±500 kV hybrid HVDC circuit breaker in the Zhangbei four-terminal DC grid
the voltage distribution characteristics and distributed capacitance parameters were simulated by the three-dimensional finite element model. The influence of the factors on the voltage-sharing components’ parameters
including single-break fault
asynchronous breaking
and the influence of shield fittings
were simulated. The research results show that
single-break fault and asynchronous breaking have a little effect on the configuration of voltage-sharing
the influence of the shield is positive but small. And the parameter check considering multiple factors is required finally. The research results can provide guidance for the voltage sharing design of series multi-break no-arc fast mechanical switch.