摘要
为解决故障限流器在电网中的配置问题
提出了基于虚拟支路法的故障限流器优化配置方法。通过对母联位置的虚拟支路化
实现了故障限流器在线路与母联位置的同时优化。以故障限流器的限流成本与限流效果为优化目标
以节点短路电流、单个限流器电抗值为约束条件
对故障限流器的安装数量、阻抗值、安装位置综合考虑
建立多目标优化模型。结合改进的免疫算法
得到限流成本与限流效果综合最优方案。最后在IEEE39节点标准网络进行分析
验证了该方法在保证求解模型通用性的前提下
能得到比仅考虑线路安装情况下更全面更适合的优化方案
改进后的免疫算法较改进前能更好地收敛到最优解。
Abstract
In order to solve the configuration problem of fault current limiter in power grid
an optimal configuration method of fault current limiter based on virtual branch method is proposed. Through the virtual branch processing of the bus connection
the fault current limiter installed in the branch and bus connection is optimized simultaneously. The current limiting cost and current limiting effect of fault current limiter are taken as the optimization objectives and the node short-circuit current and the reactance value of a single fault current limiter are taken as the constraint conditions to establish a multi-objective optimization model after taking the number
impedance value and installation location of fault current limiter into comprehensive consideration. Combined with the improved immune algorithm
an optimal scheme under the consideration of current limiting cost and current limiting effect is obtained. Finally
IEEE39 node standard network is analyzed to verify that this method can obtain a more comprehensive and more suitable optimization scheme than the one only considering the line installation case on the premise of ensuring the universality of the solution model
and the improved immune algorithm can converge to the optimal solution better than before.