Insulation Design and Assessment of Critical Components in MV Power Converter
|更新时间:2025-12-08
|
Insulation Design and Assessment of Critical Components in MV Power Converter
Vol. 46, Issue 10, Pages: 3407-3417(2020)
作者机构:
西安交通大学电力设备电气绝缘国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 October 2020,
Published:2020
稿件说明:
移动端阅览
ZHANG Chongxing, WU Wenjie, XIE Jiacheng, et al. Insulation Design and Assessment of Critical Components in MV Power Converter[J]. 2020, 46(10): 3407-3417.
DOI:
ZHANG Chongxing, WU Wenjie, XIE Jiacheng, et al. Insulation Design and Assessment of Critical Components in MV Power Converter[J]. 2020, 46(10): 3407-3417.DOI:
Insulation Design and Assessment of Critical Components in MV Power Converter
The increase of power density of Si C-based medium-voltage converters is limited due to external insulation problems
and it is urgent to study its external insulation design and evaluation. First
a novel silicon photomultiplier(SiPM)-based external discharge sensor is proposed. Then
the partial discharge(PD) characteristics of two external insulation structures under PWM excitation are studied using this sensor
and universal high-voltage insulation design recommendations of power electronics are summarized. Finally
by taking the design evaluation of two key insulation components in the SiC-based medium-voltage converters as examples
insulation assessment tests are carried out with the proposed sensor. The results show that SiPM optical sensor has the advantages of small size
high sensitivity
strong anti-electromagnetic interference ability
etc.
which is suitable for power electronic applications under PWM excitation. The PD inception voltages decrease as the switching speed of the device and the frequency increase
under two typical external discharge defects. PD pulses are mainly distributed on the rising and falling edges of PWM excitation for creeping discharge
while for tip discharge
PD pulses mainly exist in the flat area of PWM excitation. The results verify the feasibility that the proposed sensor could be used in offline evaluation of converter insulation system and even future online monitoring applications. The proposed power electronic insulation design recommendations and evaluation method can provide references to the insulation design and evaluation of future medium voltage high power density converters.