Resonance Damping Characteristic Analysis of Distributed Inverter-based System with Grid Voltage Feed-forward Control in Weak Grid
|更新时间:2025-12-08
|
Resonance Damping Characteristic Analysis of Distributed Inverter-based System with Grid Voltage Feed-forward Control in Weak Grid
Vol. 46, Issue 10, Pages: 3521-3532(2020)
作者机构:
内蒙古电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 October 2020,
Published:2020
稿件说明:
移动端阅览
MIAO Lifang, WANG Yueyuan, CAO Bin, et al. Resonance Damping Characteristic Analysis of Distributed Inverter-based System with Grid Voltage Feed-forward Control in Weak Grid[J]. 2020, 46(10): 3521-3532.
DOI:
MIAO Lifang, WANG Yueyuan, CAO Bin, et al. Resonance Damping Characteristic Analysis of Distributed Inverter-based System with Grid Voltage Feed-forward Control in Weak Grid[J]. 2020, 46(10): 3521-3532.DOI:
Resonance Damping Characteristic Analysis of Distributed Inverter-based System with Grid Voltage Feed-forward Control in Weak Grid
Resonance damping characteristics of a distributed inverter-based system(DIBS) will be influenced by grid voltage feed-forward control in weak grid condition as the actual feed-forward component contains information of capacitor voltage. By taking the digital control delay into consideration
a mathematical model of grid voltage feed-forward and capacitor current feedback controlled DIBS is established. According to Mason rules
the equivalent virtual impedance formed by control loop is obtained through a set of equivalent transformation
and corresponding impedance characteristics are analyzed. Base on Bode diagrams of system open-loop gain
the influence of grid voltage feed-forward control on resonance damping characteristic of DIBS is fully discussed in the presence and absence of digital control delay. Theory analysis and simulation results show that grid voltage feed-forward can shift resonance frequency under the both conditions. In addition
the damping performance of capacitor-current feedback control can be improved
and the robustness of system stability against grid impedance variation with digital control delay can be Increased.