Voltage Coefficient Measurement Method of Voltage Transformer Based on Three-port Network
|更新时间:2025-12-08
|
Voltage Coefficient Measurement Method of Voltage Transformer Based on Three-port Network
Vol. 47, Issue 2, Pages: 480-486(2021)
作者机构:
1. 武汉大学电气与自动化学院
2. 中国电力科学研究院有限公司国家高电压计量站
3. 华中科技大学强电磁工程与新技术国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:28 February 2021,
Published:2021
稿件说明:
移动端阅览
LAN Lei, YIN Xiaodong, LIU Hao, et al. Voltage Coefficient Measurement Method of Voltage Transformer Based on Three-port Network[J]. 2021, 47(2): 480-486.
DOI:
LAN Lei, YIN Xiaodong, LIU Hao, et al. Voltage Coefficient Measurement Method of Voltage Transformer Based on Three-port Network[J]. 2021, 47(2): 480-486.DOI:
Voltage Coefficient Measurement Method of Voltage Transformer Based on Three-port Network
To eliminate the error of voltage coefficient measurement caused by shielding leakage and adjacent interference in the transformer series voltage summation
a measurement method for the voltage coefficient of two-stage transformers in series based on three-port network is proposed. Firstly
the types and sources of additional errors in series voltage summation of transformers are analyzed. The passive linear three-port network voltage proportional-value model in which additional errors are taken into consideration is established based on the series voltage summation of two-stage transformers. The output response of the three-port network model is proved to possess linear superposition by circuit theory. Then
in the
process of solving voltage coefficient
the new three-step recursive measurement method and iterative algorithm are proposed based on the traditional series summation. Derivation proves that this method can be adopted to eliminate the influences of shielding leakage and adjacent interference. Finally
for the same 110/
1/2
3 kV voltage transformer
the two-stage transformer series method proposed in this paper is compared with the German physikalisch-technische bundesanstalt(PTB). And for the same 220/
1/2
3 kV voltage transformer
the method in this paper is compared with the traditional series summation. The results show that the deviation of the international comparison is less than the ratio error of 2×10
–6
and the phase error of 2 μrad
and the two-stage transformer series method proposed in this paper is better than traditional summation method. This research can provide support for improving the accuracy of traceability of power frequency voltage ratio standard system in China.