Measurement and Assessment Method of Contact Resistance Between Grounding Conductor and Soil and Its Application
|更新时间:2025-12-08
|
Measurement and Assessment Method of Contact Resistance Between Grounding Conductor and Soil and Its Application
Vol. 47, Issue 2, Pages: 687-694(2021)
作者机构:
1. 贵州电网有限责任公司电力科学研究院
2. 武汉大学电气与自动化学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:28 February 2021,
Published:2021
稿件说明:
移动端阅览
ZHANG Xun, ZENG Peng, HUANG Daochun, et al. Measurement and Assessment Method of Contact Resistance Between Grounding Conductor and Soil and Its Application[J]. 2021, 47(2): 687-694.
DOI:
ZHANG Xun, ZENG Peng, HUANG Daochun, et al. Measurement and Assessment Method of Contact Resistance Between Grounding Conductor and Soil and Its Application[J]. 2021, 47(2): 687-694.DOI:
Measurement and Assessment Method of Contact Resistance Between Grounding Conductor and Soil and Its Application
摘要
接地体与土壤的接触电阻是接地网电阻的重要组成部分
但目前接地网设计中通常认为接地体和土壤是理想接触的
土壤颗粒度大时可能给地网设计带来较大误差。论文提出了一种研究接地体和土壤接触电阻的测试评估方法
建立了接地体与土壤接触电阻的测试平台
结合仿真计算对比了石墨基柔性接地材料和圆钢在不同土壤类型条件下的接触特性
并提出在仿真设计中通过等效涂层的方式模拟接触电阻。研究表明:该方法能有效评估接地体和土壤的接触电阻
石墨基柔性接地材料的接触性能在典型山石地区的土壤条件下明显优于圆钢
石墨基柔性接地材料与土壤的接触电阻占工频接地电阻的1.83%~1.95%
而圆钢占比为6.79%~7.57%。
Abstract
The contact resistance between grounding materials and soil is an important part of grounding resistance of grounding grids. However
at present
the design of grounding grids usually assumes that the grounding materials and soil are in ideal contact
which may bring a large error to the design value of grounding resistance. In this paper
a method for measuring and assessing the contact resistance between grounding materials and soil was proposed. A test platform for the contact resistance between grounding materials and soil was established. Then
combined with the finite element simulation
the contact characteristics of graphite based flexible grounding material and round steel with several soil types were compared. Finally
it was proposed to simulate the contact resistance through an equivalent coating in the simulation design of grounding grids. The research results show that the method of this paper can be adopted to effectively assess the contact resistance between the grounding materials and the soil
and the contact characteristics between graphite based flexible grounding material and typical mountainous soil is significantly better than that of round steel. The contact resistance between graphite based flexible grounding material and soil accounts for 1.83%~1.95% of the power frequency grounding resistance
while the contact resistance between round steel and soil accounts for 6.79%~7.57%.