Broken Fault Detection Method of Down Conductor in Wind Turbine Blade Based on Nanosecond-pulse Reflection and Location
|更新时间:2025-12-08
|
Broken Fault Detection Method of Down Conductor in Wind Turbine Blade Based on Nanosecond-pulse Reflection and Location
Vol. 47, Issue 3, Pages: 1100-1108(2021)
作者机构:
1. 新能源电力系统国家重点实验室(华北电力大学)
2. 国网新源张家口风光储示范电站有限公司
3. 国网冀北电力有限公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2021,
Published:2021
稿件说明:
移动端阅览
LI Hongbo, LI Qingmin, GUO Zixin, et al. Broken Fault Detection Method of Down Conductor in Wind Turbine Blade Based on Nanosecond-pulse Reflection and Location[J]. 2021, 47(3): 1100-1108.
DOI:
LI Hongbo, LI Qingmin, GUO Zixin, et al. Broken Fault Detection Method of Down Conductor in Wind Turbine Blade Based on Nanosecond-pulse Reflection and Location[J]. 2021, 47(3): 1100-1108.DOI:
Broken Fault Detection Method of Down Conductor in Wind Turbine Blade Based on Nanosecond-pulse Reflection and Location
摘要
风机叶片防雷系统故障会严重影响风机的安全运行
多数风机叶片引下线在分支与主引下线的连接处常出现断裂故障。该文基于行波传输原理
提出了一种风机叶片引下线分支点断裂故障的检测与定位方法。首先
通过理论分析和仿真
讨论了纳秒脉冲信号在叶片引下线多分支结构中的传播过程对识别故障反射波的影响;然后
为解决故障波形中故障反射波被掩盖的问题
引入了"差异反推法"
并依据故障分支结构处产生的脉冲簇的幅值发生变化这一特点
利用作差将故障反射波提取出来
通过寻找作差波形中的故障反射波来定位故障分支点;最后
对某2.5 MW真机叶片引下线可能出现的所有故障情况进行了多次实验
其结果验证了该文所提方法的有效性。该文提出的方法具有较好的适用性
可用于检测与定位不同型号风机叶片引下线的分支点断裂故障。
Abstract
The interception failure of a wind turbine blade lightning protection system will seriously affect the safe operation of a wind turbine. Broken faults often occur in the connection between the branch and the main down conductor of most wind turbine blades. In this paper
a method is proposed to detect and locate the branch broken fault in the blade down conductor of wind turbine
based on the principle of traveling wave transmission. First
through theoretical analysis and simulation
the influence of the propagation process of the nanosecond pulse signal in the multi-branch structure of the blade down conductor on the identification of the fault-reflected wave is discussed. Then
in order to solve the problem that the fault reflected wave is hidden in the fault waveform
the "difference deduction method" is introduced. And according to the characteristic that the amplitude of the pulse cluster generated at the fault branch structure changes
the fault reflected wave is extracted by the difference
and the fault branch point is located by looking for the fault reflected wave in the difference waveform. Finally
a blade down conductor of a 2.5 MW real wind turbine is employed to verify the proposed method and the experimental results prove its effectiveness. The proposed method has good applicability and can be applied to detect and locate the branch broken fault in blade down conductor of any type of wind turbine.