Fault Location Method and Engineering Application in UHV GIL Based on Transient Voltage Monitoring
|更新时间:2025-12-08
|
Fault Location Method and Engineering Application in UHV GIL Based on Transient Voltage Monitoring
Vol. 47, Issue 3, Pages: 1092-1099(2021)
作者机构:
1. 清华四川能源互联网研究院
2. 国家电网有限公司
3. 清华大学电机工程与应用电子技术系电力系统及发电设备控制和仿真国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2021,
Published:2021
稿件说明:
移动端阅览
DING Dengwei, HAN Xiancai, ZHANG Pengfei, et al. Fault Location Method and Engineering Application in UHV GIL Based on Transient Voltage Monitoring[J]. 2021, 47(3): 1092-1099.
DOI:
DING Dengwei, HAN Xiancai, ZHANG Pengfei, et al. Fault Location Method and Engineering Application in UHV GIL Based on Transient Voltage Monitoring[J]. 2021, 47(3): 1092-1099.DOI:
Fault Location Method and Engineering Application in UHV GIL Based on Transient Voltage Monitoring
In case of insulation breakdown accident of ultra-high voltage(UHV) gas insulated metal-enclosed transmission line(GIL)
the accurate location of breakdown position is conducive to emergency repair and rapid recovery of power transmission. This paper proposes a fault location method based on transient voltage monitoring for UHV GIL
which is actually applied in 1 100 kV Sutong GIL utility tunnel project. The system includes voltage sensor
monitoring terminal
and storage and control unit
which are successfully installed and implemented. During GIL field tests
when the GIL flashover occurs
the system successfully triggers and completely records the transient voltages generated during the breakdown. Through waveform analysis
it is found that when UHV GIL solid insulation breaks down
the half-wave steepening time of transient voltage is less than 130 ns and spreads between the breakdown point and bushing port
forming a typical traveling wave process. According to the time when the transient traveling wave first reaches the measuring points at both ends of GIL
combined with the propagation speed of traveling wave
the accurate position of the fault point is calculated and the fault point is quickly disassembled for maintenance. According to the results of disintegration verification
the positioning error of the system is less than 5 meters. It can be seen that the adoption of wide-band voltage sensing based on capacitive voltage divider can realize the rapid and accurate location of insulation breakdown faults of UHV GIL
which is conducive to improving the operation reliability of UHV transmission system.