Calculation of Lightning Trip Out Rate of 10 kV Distribution Lines Based on Lightning Activity Characteristics
|更新时间:2025-12-08
|
Calculation of Lightning Trip Out Rate of 10 kV Distribution Lines Based on Lightning Activity Characteristics
Vol. 47, Issue 3, Pages: 1118-1127(2021)
作者机构:
1. 武汉理工大学自动化学院
2. 广东电网清远供电局
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2021,
Published:2021
稿件说明:
移动端阅览
YAN Wei, XIAO Chun, WU Xixiu, et al. Calculation of Lightning Trip Out Rate of 10 kV Distribution Lines Based on Lightning Activity Characteristics[J]. 2021, 47(3): 1118-1127.
DOI:
YAN Wei, XIAO Chun, WU Xixiu, et al. Calculation of Lightning Trip Out Rate of 10 kV Distribution Lines Based on Lightning Activity Characteristics[J]. 2021, 47(3): 1118-1127.DOI:
Calculation of Lightning Trip Out Rate of 10 kV Distribution Lines Based on Lightning Activity Characteristics
The intensity of lightning activity and the randomness of lightning points are the main factors that affect the lightning trip rate. In order to comprehensively consider the regional differences and randomness of lightning activities and improve the calculation accuracy of lightning trip rate
a lightning trip rate calculation model based on the Monte Carlo method considering the characteristics of lightning activity is established. According to the principle of lightning trip
a function expression of lightning trip rate which is only related to the lightning activity intensity
and the randomness parameters of lightning point is established. In order to consider the characteristics of lightning activity
the lightning data of the lightning location system(LLS) are utilized
the outlier analysis is performed using the median absolute deviation method
and a cumulative probability distribution model of lightning current magnitude and ground lightning density are obtained by using nonlinear least square method and descriptive statistical method. The Monte Carlo method is used to solve the random problems such as the location of lightning strike
the magnitude of lightning current
and the lightning strike line. In order to consider the influence of trees and buildings
an improved electrical geometric model method based on shielding factors is proposed to determine the range of lightning. Based on the above work
a calculation model of lightning trip rate of 10 kV distribution lines based on the Monte Carlo method considering the characteristics of lightning activity is established. The research results show that the final calculation result is 17.46 times/(100 km·a)
and the error is only 1.4% compared with the actual statistical result of 17.22 times/(100 km·a). The statistical results of actual lightning parameters are used to optimize the calculation of the lightning trip rate and significantly improve the accuracy of the results.