Design of Detection System and Harmonic Characteristic Analysis for the Grid Side Winding Current of UHVDC Converter Transformer
|更新时间:2025-12-08
|
Design of Detection System and Harmonic Characteristic Analysis for the Grid Side Winding Current of UHVDC Converter Transformer
Vol. 47, Issue 4, Pages: 1443-1450(2021)
作者机构:
1. 华北电力大学河北省输变电设备安全防御重点实验室
2. 中国电力科学研究院有限公司
3. 国家电网有限公司
4. 国网河南省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2021,
Published:2021
稿件说明:
移动端阅览
ZHAO Tao, LIU Lekang, SUN Jiantao, et al. Design of Detection System and Harmonic Characteristic Analysis for the Grid Side Winding Current of UHVDC Converter Transformer[J]. 2021, 47(4): 1443-1450.
DOI:
ZHAO Tao, LIU Lekang, SUN Jiantao, et al. Design of Detection System and Harmonic Characteristic Analysis for the Grid Side Winding Current of UHVDC Converter Transformer[J]. 2021, 47(4): 1443-1450.DOI:
Design of Detection System and Harmonic Characteristic Analysis for the Grid Side Winding Current of UHVDC Converter Transformer
Based on the on-site detection requirements of winding current and generation mechanism of the harmonic current in the converter station
this paper presents a system for detecting harmonic current in the grid side windings of the converter transformer to obtain the winding current harmonic and analyzes its influence on power loss
internal temperature rise and vibration noise of the transformer. The technologies of current signal extraction
signal synchronous acquisition
optical fiber transmission
and harmonic cluster frequency algorithm are combined in the winding harmonic current detection system. Under the steady-state operation condition of bipolar equilibrium constant power
the effectiveness of the detection system is verified by the results of on-site detection and the simulation analysis of the harmonic characteristics. Based on this
the harmonic current of the grid side winding is detected and analyzed during the process of dc transmission power rise. The results show that
with the increase of DC transmission power
the distortion rates of 11 th
17 th
19 th
23 rd
29 th
31 st
35 th
37 th
41 st
43 rd
47 th and 49 th harmonics have a significant decline trend
and the total harmonic distortion rate reduces gradually.