Design and Application of Short Circuit Test Scheme for Hybrid DC Circuit Breakers in Zhoushan VSC-HVDC Transmission Project
|更新时间:2025-12-08
|
Design and Application of Short Circuit Test Scheme for Hybrid DC Circuit Breakers in Zhoushan VSC-HVDC Transmission Project
Vol. 47, Issue 4, Pages: 1428-1435(2021)
作者机构:
1. 浙江大学工程师学院
2. 国网浙江省电力公司电力科学研究院
3. 华北电力大学新能源电力系统国家重点实验室
4. 全球能源互联网研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2021,
Published:2021
稿件说明:
移动端阅览
QIU Peng, XUAN Xiaohua, LU Yi, et al. Design and Application of Short Circuit Test Scheme for Hybrid DC Circuit Breakers in Zhoushan VSC-HVDC Transmission Project[J]. 2021, 47(4): 1428-1435.
DOI:
QIU Peng, XUAN Xiaohua, LU Yi, et al. Design and Application of Short Circuit Test Scheme for Hybrid DC Circuit Breakers in Zhoushan VSC-HVDC Transmission Project[J]. 2021, 47(4): 1428-1435.DOI:
Design and Application of Short Circuit Test Scheme for Hybrid DC Circuit Breakers in Zhoushan VSC-HVDC Transmission Project
The short circuit test of voltage-sourced converter based high voltage direct current(VSC-HVDC) power grid with hybrid DC circuit breaker is still a blank in the world. In order to test the fault clearance reliability of DC circuit breaker and the logic of cooperation with the VSC valve
it is necessary to carry out short circuit tests in VSC-HVDC transmission projects. The electromagnetic environment data around the circuit breaker need to be acquired in the tests
which can accumulate experience for similar tests in the future. Based on the Dinghai VSC Converter Station of Zhoushan 200 kV DC Grid equipped with hybrid DC circuit breakers
this paper combines with the different action logics of DC circuit breaker and VSC valve
designs three short circuit test schemes in this converter station
including positive pole-to-ground fault
negative pole-to-ground fault
and pole-to-pole fault. These schemes overcome the difficulty of artificial short circuit faults in cable transmission systems. In the application
the action logic of the DC circuit breaker breaking and the converter valve not being blocked under a pole-to-ground fault was verified
the pole-to-pole short-circuit tests of the VSC-HVDC power grid were completed for the first time
and the transient voltage
current
and electromagnetic field data of DC side were obtained. It provides technical support for the research of hybrid DC circuit breaker and subsequent HVDC transmission projects.