Improved Droop Control Strategy for Parallel Operation of Cascaded Power Electronic Transformers
|更新时间:2025-12-08
|
Improved Droop Control Strategy for Parallel Operation of Cascaded Power Electronic Transformers
Vol. 47, Issue 4, Pages: 1274-1282(2021)
作者机构:
南京南瑞继保电气有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2021,
Published:2021
稿件说明:
移动端阅览
WEI Xing, ZHU Xinshun, GE Jian, et al. Improved Droop Control Strategy for Parallel Operation of Cascaded Power Electronic Transformers[J]. 2021, 47(4): 1274-1282.
DOI:
WEI Xing, ZHU Xinshun, GE Jian, et al. Improved Droop Control Strategy for Parallel Operation of Cascaded Power Electronic Transformers[J]. 2021, 47(4): 1274-1282.DOI:
Improved Droop Control Strategy for Parallel Operation of Cascaded Power Electronic Transformers
In order to improve the static and dynamic performance of cascaded power electronic transformers(PETs) in parallel operation
an improved droop control strategy is proposed on the basis of the traditional droop control. Firstly
the equivalent circuit of the traditional droop control for parallel system is established
and the reasons for the problems such as large voltage control deviation
low current sharing control accuracy and poor dynamic characteristics are studied. Then
the closed-loop control realizes the compensation of the output voltage control deviation
and the Taylor-expansion of the function of the load current and the phase shift angle is derived and linearized to use as the current feedforward coefficient
thus the accuracy of voltage control and the balance of current control in static performance
as well as the rapid adjustment ability in dynamic performance
can be improved. Finally
the common DC bus voltage is used to replace the output voltage of each PET as the control feedback
which reduces the influence of the line impedance on the current sharing. The experimental results of a set of 3 PETs in a parallel system show that the improved droop control strategy can reduce the power dispersion of the parallel system to 0.18% and the DC voltage control deviation to 0.2 V
which verifies the effectiveness
feasibility and practicability of the engineering application.