Research on Integrated Management of MMC-UPQC Power Quality Based on Passivity Control Under Unbalanced Grid
|更新时间:2025-12-08
|
Research on Integrated Management of MMC-UPQC Power Quality Based on Passivity Control Under Unbalanced Grid
Vol. 47, Issue 4, Pages: 1344-1355(2021)
作者机构:
1. 国家电网有限公司华东分部
2. 上海市电站自动化技术重点实验室(上海电力大学自动化工程学院)
3. 国网上海市电力有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2021,
Published:2021
稿件说明:
移动端阅览
刘亨铭, 江畅, 程启明, et al. Research on Integrated Management of MMC-UPQC Power Quality Based on Passivity Control Under Unbalanced Grid[J]. 2021, 47(4): 1344-1355.
DOI:
刘亨铭, 江畅, 程启明, et al. Research on Integrated Management of MMC-UPQC Power Quality Based on Passivity Control Under Unbalanced Grid[J]. 2021, 47(4): 1344-1355.DOI:
Research on Integrated Management of MMC-UPQC Power Quality Based on Passivity Control Under Unbalanced Grid
The unified power quality converter(UPQC) of modular multilevel converter(MMC) can be used for recovering power quality of voltage and current under high voltage
whereas it is difficult to comprehensively control the power quality when the voltage imbalance of the grid is remarkable. Therefore
the passive control method was applied to MMC-UPQC to solve the power quality problems under voltage imbalance. Firstly
based on the topological structure of MMC-UPQC
the mathematical model of MMC-UPQC was established under unbalanced power network. Secondly
the detection quantity was separated without phase-locked loop through a method of positive and negative sequence separation. Thirdly
based on the passive control theory
the PBC controller based on the E-L model was built and applied to power quality compensation system under multi-level and high-voltage. Finally
the principles of series side compensation voltage and parallel side compensation current were applied to the coordinated control for comprehensively solving the power quality problem of the grid under unbalanced state. The experimental results on the Matlab/Simulink platform show that the response time of the MMC-UPQC system based on the proposed passive controller is less than 0.05 s and the total harmonic distortion is less than 5%
which verifies the certain effectiveness and superiority in solving the problem of integrated power quality management.