Effect of Lightning Return Stroke Speed on Accuracy of Inversed Return Stroke Peak Current Using Lightning Location System
|更新时间:2025-12-08
|
Effect of Lightning Return Stroke Speed on Accuracy of Inversed Return Stroke Peak Current Using Lightning Location System
Vol. 47, Issue 5, Pages: 1617-1624(2021)
作者机构:
1. 南瑞集团有限公司(国网电力科学研究院)
2. 国网电力科学研究院武汉南瑞有限责任公司
3. 电网雷击风险预防湖北省重点实验室
4. 合肥工业大学电气与自动化工程学院
5. 中车唐山机车车辆有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 May 2021,
Published:2021
稿件说明:
移动端阅览
王宇, 谷山强, 孟刚, et al. Effect of Lightning Return Stroke Speed on Accuracy of Inversed Return Stroke Peak Current Using Lightning Location System[J]. 2021, 47(5): 1617-1624.
DOI:
王宇, 谷山强, 孟刚, et al. Effect of Lightning Return Stroke Speed on Accuracy of Inversed Return Stroke Peak Current Using Lightning Location System[J]. 2021, 47(5): 1617-1624.DOI:
Effect of Lightning Return Stroke Speed on Accuracy of Inversed Return Stroke Peak Current Using Lightning Location System
the return stroke speed is generally set to some fixed value between 1×10
8
m/s and 2×10
8
m/s when the nationwide lightning location systems are used to invert Cloud to Ground lightning return stroke currents. In this paper
the impact of adopting this method on the accuracy of the return stroke current inversion is discussed. Firstly
the method of using the lightning location system to invert the return stroke current is introduced
and the important influence of the speed of the return stroke on the peak current is analyzed. Secondly
based on
the relationship between the negative return stroke current and the return stroke speed proposed by Lundholm et al.
the analysis on the negative first return stroke reveals that the return stroke current below 25 kA may be underestimated
and the return stroke current above 160 kA may be overestimated. For negative subsequent return strokes
the return stroke current below 5 k A may be underestimated
and the return stroke current above 32 kA may be overestimated. Then
the return stroke speed observation results of negative first return strokes
negative subsequent return strokes
positive first return strokes and positive subsequent return strokes are summarized. It is believed that it is necessary to treat various types of return strokes in the lightning location system differently. Finally
for individual cases
the inversed return stroke currents and those measured from artificially triggered lightning and transmission towers are compared. Based on large samples obtained in Wuhan from 2012 to 2019
the cumulative probability distribution curve of the system inversed return stroke currents and the curve recommended by IEEE are compared. It is considered that the lightning location system of China’s power grid can retrieve reasonable return stroke currents
though the peak current of negative subsequent return strokes may be overestimated to a certain extent
which may be related to the fact that the return stroke speed set by the system is smaller than the actual value.