Electric Field and Discharge PSA Spectroscopy Characteristics of Circular Cut Defects at Different Positions of EPR Cable Terminal
|更新时间:2025-12-08
|
Electric Field and Discharge PSA Spectroscopy Characteristics of Circular Cut Defects at Different Positions of EPR Cable Terminal
Vol. 47, Issue 6, Pages: 2051-2061(2021)
作者机构:
1. 西南交通大学电气工程学院
2. 云南电网有限责任公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2021,
Published:2021
稿件说明:
移动端阅览
ZHOU Lijun, XING Limeng, YANG Han, et al. Electric Field and Discharge PSA Spectroscopy Characteristics of Circular Cut Defects at Different Positions of EPR Cable Terminal[J]. 2021, 47(6): 2051-2061.
DOI:
ZHOU Lijun, XING Limeng, YANG Han, et al. Electric Field and Discharge PSA Spectroscopy Characteristics of Circular Cut Defects at Different Positions of EPR Cable Terminal[J]. 2021, 47(6): 2051-2061.DOI:
Electric Field and Discharge PSA Spectroscopy Characteristics of Circular Cut Defects at Different Positions of EPR Cable Terminal
摘要
动车组用乙丙橡胶(ethylene-propylene rubber
EPR)电缆终端在安装时需人工剥除外半导电层
易造成环切缺陷进而导致放电现象
同时缺陷处易填充气体形成气隙
将加速放电发展
最终引起严重的电缆击穿故障。首先对距截断处60 mm内含环切缺陷的电缆终端进行有限元分析
计算环切处最大场强;然后在25 kV工频电压下开展放电试验
分析了PRPD和PSA谱图特征
并对PSA谱图灰度值作K-means聚类特征提取。研究结果表明
环切缺陷的位置与其对EPR电缆绝缘性能的影响密切相关
距截断处60mm以内的环切缺陷不可忽视;当连续放电脉冲电压差绝对值相等时
缺陷靠近截断处且影响极其严重
距离超过60 mm时则影响较小。结合放电特性可知
PSA谱图灰度值小于255的频数在5区的最大占比、4区的最小占比和分类聚心特征
可为判断环切缺陷位置和EPR电缆绝缘状态提供重要的理论依据和数据参照。
Abstract
Ethylene-propylene rubber cable terminals for EMUs need to be manually stripped except for the semi-conductive layer during installation
which is likely to cause circular cutting defects and lead to discharge. At the same time
the defects are easily filled with gas to form air gaps
which will accelerate the development of discharge and eventually cause severe cable impact wear failure. Firstly
a finite element analysis was performed on a cable terminal containing a ring-cut defect within 60 mm from the truncation
and the maximum field strength was calculated at the ring-cut. Then
a discharge test was performed at a power frequency of 25 kV
and the characteristics of the PRPD and PSA spectra were analyzed. The gray value of PSA spectrum was used for K-means clustering feature extraction. The results show that the location of the cireular cut defect is closely related to its influence on the insulation performance of the EPR cable
and the circular cut defect within 60 mm from the cut-off point can not be ignored. When the continuous discharge pulse voltage difference meets the same absolute value
the defect is close to the truncation and the impact is extremely serious
and the effect is smaller when the distance exceeds 60 mm. Combined with the discharge characteristics
it can be seen that the parameters
such as the frequency of the PSA spectrum with a gray value of less than 255 in the maximum proportion in zone 5
the minimum proportion in zone 4
and the classification centering feature
can provide important information for judging the location of the circumcision defect and the insulation status of the EPR cable theoretical basis and data reference.