Quantitative Analysis Method for Raman Spectral Detection of Methanol Dissolved in Transformer Oil
|更新时间:2025-12-08
|
Quantitative Analysis Method for Raman Spectral Detection of Methanol Dissolved in Transformer Oil
Vol. 47, Issue 6, Pages: 2007-2014(2021)
作者机构:
广东电网有限责任公司广州供电局
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2021,
Published:2021
稿件说明:
移动端阅览
LI Guangmao, QIAO Shengya, ZHU Chen, et al. Quantitative Analysis Method for Raman Spectral Detection of Methanol Dissolved in Transformer Oil[J]. 2021, 47(6): 2007-2014.
DOI:
LI Guangmao, QIAO Shengya, ZHU Chen, et al. Quantitative Analysis Method for Raman Spectral Detection of Methanol Dissolved in Transformer Oil[J]. 2021, 47(6): 2007-2014.DOI:
Quantitative Analysis Method for Raman Spectral Detection of Methanol Dissolved in Transformer Oil
Methanol dissolved in transformer oil is an important characteristic quantity to characterize the aging of oil-paper insulation
thus
developing an efficient
accurate and suitable detection method for the on-site determination of methanol content in transformer oil is of great significance. Raman spectroscopy technique has the advantages of fast response
easy operation
and non-destructive testing
and has been widely used in the fields of chemistry
materials and biology research. Therefore
we employed the GAUSSIAN software to construct and calculate the Raman spectra of methanol molecule
water molecule and their binding model
and analyzed the reasons for the shift of each peak. The laser Raman spectroscopy detection platform was constructed to detect the methanol Raman spectra in the transformer oil after ultrapure water extraction. The quantitative analysis model was constructed by combining the least square method. The minimum detection limit for methanol was 15.6 mg/L
and the goodness of fit was 0.997 94. The application of Raman spectroscopy combined with liquid phase extraction in the detection of methanol in transformer oil has a good effect
and it provides a new idea for the accurate detection of aging features.
Raman Analysis on Characteristic Gases in Transformer Oil Based on Kurtosis
Quantitative Risk Assessment of Distribution Network Based on Real-time Health Index of Equipment
Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection
Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method
Related Author
WANG Pinyi
WEI Yulai
WANG Jianxin
CHEN Weigen
SONG Ruimin
WANG Ziyi
TAN Yumiao
MA Jun
Related Institution
输变电装备技术全国重点实验室(重庆大学电气工程学院)
Chongqing Engineering Research Center of Energy Internet
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University
School of Electrical and Electronic Engineering, Chongqing University of Technology