Application of FBGs to Brittle Fracture Monitoring of Rods in Composite Insulators
|更新时间:2025-12-08
|
Application of FBGs to Brittle Fracture Monitoring of Rods in Composite Insulators
Vol. 47, Issue 6, Pages: 1998-2006(2021)
作者机构:
华南理工大学电力学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2021,
Published:2021
稿件说明:
移动端阅览
HAO Yanpeng, CAO Hangyu, WEI Jie, et al. Application of FBGs to Brittle Fracture Monitoring of Rods in Composite Insulators[J]. 2021, 47(6): 1998-2006.
DOI:
HAO Yanpeng, CAO Hangyu, WEI Jie, et al. Application of FBGs to Brittle Fracture Monitoring of Rods in Composite Insulators[J]. 2021, 47(6): 1998-2006.DOI:
Application of FBGs to Brittle Fracture Monitoring of Rods in Composite Insulators
摘要
复合绝缘子脆断是恶性事故
为此研究复合绝缘子脆断监测技术
在10 kV复合绝缘子非耐酸芯棒表面粘贴4根光纤
其中1根级联2个温度光栅
另外3根各级联5个应力光栅
进行温度标定试验、拉力标定试验和应力腐蚀试验。结果表明
非耐酸芯棒应力腐蚀试验中出现了3个裂纹
其中1个裂纹为脆断断口
其余2个裂纹未脆断。表面多个光栅实现了非耐酸芯棒完整脆断过程的温度与应力监测
发现芯棒应力腐蚀分为4个阶段
阶段1初期无变化
阶段2腐蚀放热
阶段3裂纹起裂
阶段4裂纹快速发展至断裂。从阶段2开始腐蚀区放热
最高高于环境温度2.46℃
温差1℃可以作为复合绝缘子脆断过程中腐蚀放热阶段的早期预警阈值。应力光栅对裂纹的轴向检测距离约20 mm
The brittle fracture of composite insulators is a malignant fracture accident.Therefore
we investigated the brittle fracture monitoring of composite insulators. Four optical fibers were pasted on the surface of the fiber-reinforced plastic(FRP) rod of a 10 kV composite insulator
one of which has 2 fiber Bragg gratings(FBGs) to measure temperatures
and the others have 5 FBGs to measure stresses. Temperature calibration tests
tension calibration tests
and stress corrosion tests were carried out on the rod with surface-encapsulated FBGs. The results showed that three cracks appeared in the stress corrosion tests of the rod
of which crack 1 developed into a brittle fracture
and
the other two did not. The temperatures and the stresses in the entire brittle fracture process of the rod were monitored by the FBGs on the rod surface. It is found that the stress corrosion process can be divided into four stages as follows:no change in the initial stage
corrosive heat release in the second stage
crack initiation in the third stage
and finally
the cracks developing rapidly until the rod break. From the second stage
the heat begins to emit in the corrosion zone
and the maximum difference between the corrosion zone temperature and the ambient temperature reaches 2.46 ℃
thus a temperature difference of 1 ℃ can be used as an early warning for the second stage in the brittle fractures of composite rods. The stress FBGs can detect a crack with an axial distance of 20 mm between them
and a wavelength shift 1.1λ
wmax
or 0.9λ
wmin
of the stress FBGs can be used as an early warning for a crack initiation or a serious crack in the brittle fracture process of composite insulators
respectively. By the FBGs monitoring method in this paper
a technical means can be provided to investigate fracture mechanisms and materials against brittle fracture/decay-like fracture of composite insulators.
Field Test Research on Temperature Detection of Overhead Transmission Line Based on BOTDR Distributed Fiber Sensing Technology
Validity of Noise Reduction Method in Dielectric Loss On-line Monitoring
On-line Power Cable Partial Discharge Localisation Method Based on Cable Transfer Function and Detected Pulse Rise-time
Experimental Studies on Application Characteristics of Lightning Protection for Long Rod Suspension Composite Insulators for High-speed Railway Catenary
Research on an Online Monitoring Device for Transformer Winding Deformation Using NICS Pulse Injection Method
Related Author
CAO Min
GAN Jiulin
HUANG Jichao
SHI Zunwei
YANG Lin
XU Zhiniu
TIAN Zhi
ZHANG Leiqi
Related Institution
Yunnan Electric Power Research Institute
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources,North China Electric Power University
School of Electircal Engineering, Wuhan University
Wuhan Power Supply Company,State Grid Hubei Electic Power Company