Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization
|更新时间:2025-12-08
|
Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization
Vol. 47, Issue 8, Pages: 2820-2827(2021)
作者机构:
1. 国网江苏省电力有限公司检修分公司
2. 东南大学电气工程学院
3. 青岛理工大学信息与控制工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2021,
Published:2021
稿件说明:
移动端阅览
SHE Changjia, ZHENG Jianyong, HE Jiahong, et al. Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization[J]. 2021, 47(8): 2820-2827.
DOI:
SHE Changjia, ZHENG Jianyong, HE Jiahong, et al. Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization[J]. 2021, 47(8): 2820-2827.DOI:
Ultrasonic Localization Method of Transformer Partial Discharge by Time Difference Screening and ABC Secondary Optimization
To locate the partial discharge(PD) source in a transformer
an ultrasonic localization method by time difference screening(TDS) and artificial bee colony(ABC) secondary optimization is proposed. Firstly
the time difference of received signals is estimated by the generalized cross-correlation method. On this basis
the time-difference screening link based on spherical equations is added to eliminate the time-difference with large errors. Secondly
the constrained optimization model of spatial localization is set up according to the effective time-difference and solved by ABC algorithm. The K-Means clustering analysis is carried out for some localization results. Finally
the ABC algorithm is used to optimize the minimum point of the sum of distance clustering centers
and the localization result with large error is corrected. The simulation results show that the localization error of the method in this paper is more negligible than that of the traditional method
and the localization error is less than 5 cm in the field experiment.