DC Control Strategy for Suppressing Large-scale WTG Tripping Caused by Mono-polar Block Fault
|更新时间:2025-12-08
|
DC Control Strategy for Suppressing Large-scale WTG Tripping Caused by Mono-polar Block Fault
Vol. 47, Issue 10, Pages: 3528-3537(2021)
作者机构:
新疆大学电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 October 2021,
Published:2021
稿件说明:
移动端阅览
ZHANG Qirui, LI Fengting, YIN Chunya, et al. DC Control Strategy for Suppressing Large-scale WTG Tripping Caused by Mono-polar Block Fault[J]. 2021, 47(10): 3528-3537.
DOI:
ZHANG Qirui, LI Fengting, YIN Chunya, et al. DC Control Strategy for Suppressing Large-scale WTG Tripping Caused by Mono-polar Block Fault[J]. 2021, 47(10): 3528-3537.DOI:
DC Control Strategy for Suppressing Large-scale WTG Tripping Caused by Mono-polar Block Fault
To solve the problem that transient overvoltage of AC system will lead to the wind turbine generator(WTG)overvoltage tripping in DC near area under the mono-polar block fault
the influence mechanism of mono-polar block on transient overvoltage is analyzed
and it is pointed out that the excessive reactive power of AC system is the fundamental cause of the transient overvoltage. The characteristics of sound pole under mono-polar block fault are analyzed;in the meantime
by taking the balance state of reactive power at sending bus as regulation target
the expression of DC current command value of sound pole is derived
and the DC control strategy to suppress transient overvoltage is proposed. When the transient overvoltage can not be completely suppressed
under this improved control strategy
a coordinated control strategy is proposed to further suppress the transient overvoltage by putting into a reasonable capacity to avoid the WTG overvoltage tripping. Finally
the improved CIGRE HVDC bipolar standard system and TZ HVDC transmission system are set up on the DIgSILENT simulation platform. It is verified that the strategy can effectively block the transmission of transient overvoltage and inhibit the large-scale WTG overvoltage tripping.
Effect of Commutation Failure on the Overvoltage on Rectifier Station in AC/DC Hybrid Power System With Wind Farms
Online Detecting Winding Deformation of Power Transformer Based on Transient Overvoltage
Simulation and Test of Electromagnetic Interference with Electronic Current Transformer
Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC
Equalization Design of Isolated Power Supply Transformer for 200 kV DC Circuit Breaker
Related Author
ZENG Liang
ZHANG Yunke
SUN Guangyu
LI Yongli
ZHAO Xueming
LI Zhaojiong
CHEN Xiaohan
LI Chengxiang
Related Institution
Key Laboratory of Smart Grid of Ministry of Education, Tianjin University
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University
School of Electrical Engineering, Dalian University of Technology
Northwest Power Dispatching and Control Sub-center