Electromagnetic Disturbance Coupling and Suppression of On-site Electronic Device Power Port in Substations
|更新时间:2025-12-08
|
Electromagnetic Disturbance Coupling and Suppression of On-site Electronic Device Power Port in Substations
Vol. 47, Issue 12, Pages: 4483-4492(2021)
作者机构:
1. 清华大学电机工程与应用电子技术系电力系统及发电设备控制和仿真国家重点实验室
2. 清华四川能源互联网研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 December 2021,
Published:2021
稿件说明:
移动端阅览
GE Siqiao, LIU Weidong, DING Dengwei, et al. Electromagnetic Disturbance Coupling and Suppression of On-site Electronic Device Power Port in Substations[J]. 2021, 47(12): 4483-4492.
DOI:
GE Siqiao, LIU Weidong, DING Dengwei, et al. Electromagnetic Disturbance Coupling and Suppression of On-site Electronic Device Power Port in Substations[J]. 2021, 47(12): 4483-4492.DOI:
Electromagnetic Disturbance Coupling and Suppression of On-site Electronic Device Power Port in Substations
摘要
变电站的断路器和隔离开关操作能够产生暂态地电位升(transient earth voltage rise
TEVR)和强烈的空间电磁辐射
对变电站就地化电子装置造成严重电磁骚扰。就地化电子装置的供电电源是电磁骚扰的主要耦合路径
因此研究了供电电源电磁骚扰的耦合机理和抑制措施。研究结果表明
现有的就地化电子装置的供电电路大部分包含有连接在屏蔽箱内外之间的电源线
能够显著降低屏蔽箱的效能
将外部的电磁骚扰引入到屏蔽箱内部。提出了一种隔离变压器结构
其原边和副边绕组分别位于屏蔽箱内外
避免了跨屏蔽箱连接的电源线
试验证明其可以有效抑制供电电源引入的电磁骚扰。
Abstract
The operation of circuit breakers and disconnectors in substations can produce transient earth voltage rise(TEVR) and severe space electromagnetic radiation
causing serious electromagnetic disturbance to the on-site electronic devices in substations. The power supply of on-site electronic devices is a major coupling path of electromagnetic disturbance. Therefore
this paper studies the coupling characteristics and suppression of electromagnetic disturbance caused by on-site power supply. The research results show that most of the existing power supply circuits of on-site electronic devices contain power lines connected between the inside and outside of the shielding
which can significantly reduce the efficiency of the shielding and further introduce external electromagnetic disturbance into the shielding. In this paper
an isolation transformer structure is proposed. Its primary and secondary windings are located inside and outside the shielding box respectively
averting the power lines connected across the shielding. Further experiments on this isolation transformer show that the electromagnetic disturbance introduced by the power supply can be effectively suppressed.
Modeling and Characteristic Analysis of Switching Transient Disturbance in Substation
Measurement Method and System for Transient Platform Potential Rise and Electromagnetic Disturbance of Ultra-high Voltage Series Compensation Device
Calculation and Analysis on Electromagnetic Disturbance of Shielded Cables in Impulse Test
Research Progress in Electromagnetic Disturbance Characteristics and Protection Due to Switching Operations of Primary and Secondary Integrated Switchgear
Research on Characteristics of AC Arc Discharge Current of Live Working Robot
Related Author
YUAN Yubo
BO Qiangsheng
JI Jianfei
QIAN Jiabin
WANG Lihui
YU Jinsong
LIU Huiwen
ZHANG Weidong
Related Institution
School of Instrument Science and Engineering,Southeast University
Electric Power Research Institute,State Grid Jiangsu Electrical Power Company
Chinese Electric Power Research Institute
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University