Influence of Silicone Rubber Content of Shed and Sheath on Composite Insulator Lifespan
|更新时间:2025-12-08
|
Influence of Silicone Rubber Content of Shed and Sheath on Composite Insulator Lifespan
Vol. 48, Issue 2, Pages: 736-752(2022)
作者机构:
1. 华北电力科学研究院有限责任公司
2. 国网冀北电力有限公司
3. 华北电力大学河北省输变电设备安全防御重点实验室
4. 国网山东省电力公司
5. 国网山西省电力公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:28 February 2022,
Published:2022
稿件说明:
移动端阅览
CHEN Yuan, XUE Wenxiang, LIU Yunpeng, et al. Influence of Silicone Rubber Content of Shed and Sheath on Composite Insulator Lifespan[J]. 2022, 48(2): 736-752.
DOI:
CHEN Yuan, XUE Wenxiang, LIU Yunpeng, et al. Influence of Silicone Rubber Content of Shed and Sheath on Composite Insulator Lifespan[J]. 2022, 48(2): 736-752.DOI:
Influence of Silicone Rubber Content of Shed and Sheath on Composite Insulator Lifespan
The silicone rubber(SR) composite insulator is the most widely used insulator in transmission lines
but its actual lifespan is only 10~20 years
which is far less than 50~100 years of the porcelain/glass insulators. Due to the risk of aging of composite insulators and the huge investment of replacement
the composite insulator used to control pollution flashover may become a serious problem for power grid in the near future. Therefore
greatly improving the lifespan of composite insulators is an urgent problem to be solved. The decay fracture and the degradation of anti pollution flashover performance are the two focuses affecting the lifespan of composite insulators. The statistics of operating composite insulators
calculation of electric field distribution
dissection of decay fracture insulators
bend-electricfield-temperaturehumidity test and low temperature mechanical properties test of SR sheath show that the alternating bending is an important cause of cracked insulators. Under the combined effect of alternating bending and low temperature
it is easy to cause the deterioration and cracking of the sheath with low SR content
thus the protection effect on the core rod and interface may be lost
and a large percentage of decay fracture insulators may occur in the insulators that are easy to bear bending load
such as compact V-strings and jump strings. The excessively strict requirement for electric erosion of sheath is a technical mistake in the development of composite insulators
which has become a bottleneck to improve the lifespan of the composite insulator. Reasonably breaking through the electric erosion parameters of current standard to achieve a substantial increase in the SR content of sheath is the key to maximize the weather ability
cold resistance
low temperature elasticity of SR and improve the lifespan of the composite insulator.