Operation State Evaluation of UHV Converter Valve Based on Multi-state Data Equalization and XGBoost
|更新时间:2025-12-08
|
Operation State Evaluation of UHV Converter Valve Based on Multi-state Data Equalization and XGBoost
Vol. 48, Issue 2, Pages: 644-652(2022)
作者机构:
1. 东南大学电气工程学院
2. 河海大学能源与电气学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:28 February 2022,
Published:2022
稿件说明:
移动端阅览
LI Xuan, MEI Fei, SHA Haoyuan, et al. Operation State Evaluation of UHV Converter Valve Based on Multi-state Data Equalization and XGBoost[J]. 2022, 48(2): 644-652.
DOI:
LI Xuan, MEI Fei, SHA Haoyuan, et al. Operation State Evaluation of UHV Converter Valve Based on Multi-state Data Equalization and XGBoost[J]. 2022, 48(2): 644-652.DOI:
Operation State Evaluation of UHV Converter Valve Based on Multi-state Data Equalization and XGBoost
In order to reduce the downtime and maintenance time of a DC system and improve the stability of converter valve operation
a state evaluation method for UHV converter valve based on multi-state data equalization and extreme gradient boost(XGBoost) is proposed. Firstly
for the main components of the thyristor converter valve
the four characteristic indexes of the thyristor component
the valve cooling component
the valve arrester and the external environment are extracted. A data preprocessing method based on isolated forest and synthetic minority oversampling technology is proposed
where the outlier samples in the data set are removed
and then the minority samples are oversampled to achieve the effectiveness and balance of the data set in each state. The preprocessed data are utilized to train the XGBoost classifier
and the optimal hyperparameters of the model are obtained based on the K-fold cross-validation and grid search method. Finally
the measured data of a converter station in Jiangsu Province are taken as an example to verify the proposed method
and the results show that the accuracy rate of the evaluation model is 97.1%
which is more accurate than traditional methods for judging the operating state of the converter valve. In addition
the model can reflect the characteristic contribution of each state quantity
and provide a basis for the maintenance of the converter valve.