Prediction Model of Dissolved Gas in Transformer Oil Based on Variational Modal Decomposition and Recurrent Neural Network with Gated Recurrent Unit
|更新时间:2025-12-08
|
Prediction Model of Dissolved Gas in Transformer Oil Based on Variational Modal Decomposition and Recurrent Neural Network with Gated Recurrent Unit
Vol. 48, Issue 2, Pages: 653-660(2022)
作者机构:
1. 西南交通大学电气工程学院
2. 广东电网有限责任公司珠海供电局
作者简介:
基金信息:
DOI:
CLC:
Published Online:28 February 2022,
Published:2022
稿件说明:
移动端阅览
XIE Le, QIU Wei, LI Zhenwei, et al. Prediction Model of Dissolved Gas in Transformer Oil Based on Variational Modal Decomposition and Recurrent Neural Network with Gated Recurrent Unit[J]. 2022, 48(2): 653-660.
DOI:
XIE Le, QIU Wei, LI Zhenwei, et al. Prediction Model of Dissolved Gas in Transformer Oil Based on Variational Modal Decomposition and Recurrent Neural Network with Gated Recurrent Unit[J]. 2022, 48(2): 653-660.DOI:
Prediction Model of Dissolved Gas in Transformer Oil Based on Variational Modal Decomposition and Recurrent Neural Network with Gated Recurrent Unit
Dissolved gas analysis in oil is an effective method for early fault diagnosis of the transformer. Accurate prediction of dissolved gas volume fraction in oil can provide a theoretical basis for early fault monitoring and early warning of the transformer. In this paper
a prediction method of dissolved gases in transformer oil based on variational mode decomposition(VMD) and recurrent neural network with gated recurrent unit(GRU-RNN) was proposed. Firstly
the original time series of dissolved gases volume fraction in oil of transformer were decomposed into sub-series by VMD to reduce the influence of instability. Then
the GRU-RNN prediction method was used to predict the sub-series in one step and multi-step
respectively. Finally
the predicted sub-series were superposed and reconstructed to obtain the one-step and multi-step prediction of dissolved gas volume fraction in transformer oil. The results show that the mean absolute error(MAE) and root mean square error(RMSE) of the method are 0.057 6 and 0.068 4
respectively
and the MAE and RMSE of the multi-step prediction are 0.167 9 and 0.204 1
respectively. Compared with other prediction methods
the proposed method in this paper has a great improvement in single-step and multi-step prediction ability
which provides a reference for the power transformer monitoring and early warning.