侯启鑫, 李庆民, 邹亮, 孙玉鑫, 刘青松. 特高压换流阀桥臂电抗器包封参数的混合约束设计方法[J]. 电网技术, 2023, 47(3): 1280-1288. DOI: 10.13335/j.1000-3673.pst.2022.0436
引用本文: 侯启鑫, 李庆民, 邹亮, 孙玉鑫, 刘青松. 特高压换流阀桥臂电抗器包封参数的混合约束设计方法[J]. 电网技术, 2023, 47(3): 1280-1288. DOI: 10.13335/j.1000-3673.pst.2022.0436
HOU Qixin, LI Qingmin, ZOU Liang, SUN Yuxin, LIU Qingsong. Hybrid Constraint Design for Encapsulation Parameters of UHV Converter Valve Bridge Arm Reactor[J]. Power System Technology, 2023, 47(3): 1280-1288. DOI: 10.13335/j.1000-3673.pst.2022.0436
Citation: HOU Qixin, LI Qingmin, ZOU Liang, SUN Yuxin, LIU Qingsong. Hybrid Constraint Design for Encapsulation Parameters of UHV Converter Valve Bridge Arm Reactor[J]. Power System Technology, 2023, 47(3): 1280-1288. DOI: 10.13335/j.1000-3673.pst.2022.0436

特高压换流阀桥臂电抗器包封参数的混合约束设计方法

Hybrid Constraint Design for Encapsulation Parameters of UHV Converter Valve Bridge Arm Reactor

  • 摘要: 随着交直流输电工程的混联规模不断扩大,桥臂电抗器的工况日益复杂。现有设计方法不能满足复杂工况的需求,单一的设计约束难以实现综合性能优化,在工程需求多样化的发展趋势下,需要兼顾各项性能指标。提出交直流复合工况下的等效电磁模型,以工频下得到的结构参数为准,在此基础上求解其他频次的包封电流,并在计算时考虑到实际的过负荷、谐波工况;提出基于权系数的混合约束设计方法,形成包封电流密度、电阻电压和温升混合的约束条件,提出权系数调整策略,并建立目标函数量化比较不同设计算例,在此基础上,面向严苛的电抗器实际需求,另构建3种目标函数,明确优化流程,利用梯度下降法对包封结构进一步优化。针对±800kV桥臂电抗器实例,采用混合约束设计在各项指标中取了“折中”,通过样机的系列测试验证了设计方法的有效性。

     

    Abstract: With the continuous expansion of the hybrid scale of AC/DC transmission projects, the working conditions of the bridge arm reactors are becoming more and more complex. The existing designs can not meet the needs of complex working conditions, and one single design constraint is difficult to achieve comprehensive performance optimization.Under the development trend of diversified engineering needs, it is necessary to take all design indexes into account.In this paper, an equivalent electromagnetic model under AC/DC composite working conditions is proposed. Based on the structural parameters obtained at the power frequency, the encapsulation currents of the other frequencies are solved, and the actual overload and harmonic conditions are considered in the calculation; Based on the weight coefficient, a hybrid constraint design methodology is proposed, and the constraints of the combination of encapsulation current density, the resistance voltage and the temperature rise are formed. A weight coefficient adjustment strategy is proposed, meanwhile, an objective function is established to quantitatively compare different design cases. On these basis, facing the actual harsh demands of the reactor, three other objective functions are constructed, clarifying the optimization process and optimizing the encapsulation structure by using the gradient descent method. For the example of an ±800kV bridge arm reactor, the hybrid constraint design methodology reaches a 'compromise' among all indexes, the effectiveness of the design methodology verified by a series of tests of the prototype.

     

/

返回文章
返回