杨杰, MuhammadJunaid, 姜楠. GIS组合电器设备漏气气室自动保压系统[J]. 电力信息与通信技术, 2024, 22(10): 54-60. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.08
引用本文: 杨杰, MuhammadJunaid, 姜楠. GIS组合电器设备漏气气室自动保压系统[J]. 电力信息与通信技术, 2024, 22(10): 54-60. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.08
YANG Jie, Muhammad Junaid, JIANG Nan. An Automatic Pressure Maintaining System for the Leakage Chamber of GIS[J]. Electric Power Information and Communication Technology, 2024, 22(10): 54-60. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.08
Citation: YANG Jie, Muhammad Junaid, JIANG Nan. An Automatic Pressure Maintaining System for the Leakage Chamber of GIS[J]. Electric Power Information and Communication Technology, 2024, 22(10): 54-60. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.08

GIS组合电器设备漏气气室自动保压系统

An Automatic Pressure Maintaining System for the Leakage Chamber of GIS

  • 摘要: 近年来,随着气体绝缘金属封闭开关(gas insulated switcher,GIS)组合电器成为110 kV及以上变电站的主流使用设备,其设备因为产品质量、安装工艺和复杂环境等导致的漏气问题也逐渐凸显出来。GIS漏气缺陷因涉及停电计划、施工周期和工艺难度等问题往往不能得到及时处理。文章提出一种GIS组合电器设备漏气气室自动保压系统,该系统具备以下特性:可实现自动控制补气,使漏气气室在压力降到报警值时及时得到补充;可实现人工远程和自动控制、就地控制多模式操作;采用电磁阀和止回阀结合的双保险结构,可有效防止设备在补气过程中的气体倒灌;采用并联SF6气瓶组的方式为自动补气系统提供充足气体压力,并可动态监测气瓶组气压状态,且具备低气压远程报警功能,及时提醒检修人员更换气瓶;该系统可通过计数功能统计气室的漏气速率并上传后台云端,为检修人员的统计补气周期和后期解体检修提供可靠依据。通过制作一套漏气气室自动保压实物仿真系统,验证了该装置的可行性。

     

    Abstract: In recent years, the SF6 gas leakage problem of the gas insulated switcher (GIS) equipment due to the product quality, installation process and complex operating environment has gradually become prominent as the equipment of GIS has become the mainstream equipment in 110 kV and above substations. But the SF6 gas leakage defects often cannot be dealt with in time because they involve problems such as power outage plan, construction period and process difficulty. This paper presents an automatic pressure maintaining system for gas leakage chamber of GIS, which has the following characteristics: It can realize automatic control for SF6 gas replenishment, so that the SF6 gas leakage chamber can be replenished in time when the pressure drops to the alarm value. It can achieve multi-mode operation including the manual remote, automatic control and local control. The double safety structure combined with the solenoid valve and check valve can effectively forestall the gas back-flow. The SF6 cylinder group is connected in parallel to provide sufficient gas pressure, and the system can dynamically monitor the gas pressure state of the cylinder group, and has the function of low-pressure remote alarm to remind the maintenance personnel to replace the cylinder in time. The system can count the gas leakage rate through the counting function and upload it to the cloud, providing a reliable basis for the maintenance personnel to count the air replenishment cycle and disassembly maintenance. In this paper, the feasibility of the device is verified by making a physical simulation system of automatic pressure maintaining.

     

/