袁哲, 孙明辉, 颜伟. 考虑信号畸变的多源信息融合配电网故障定位方法[J]. 电力信息与通信技术, 2024, 22(10): 1-8. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.01
引用本文: 袁哲, 孙明辉, 颜伟. 考虑信号畸变的多源信息融合配电网故障定位方法[J]. 电力信息与通信技术, 2024, 22(10): 1-8. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.01
YUAN Zhe, SUN Minghui, YAN Wei. Multi-source Information Fusion Fault Localization Method for Distribution Network Considering Signal Distortion[J]. Electric Power Information and Communication Technology, 2024, 22(10): 1-8. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.01
Citation: YUAN Zhe, SUN Minghui, YAN Wei. Multi-source Information Fusion Fault Localization Method for Distribution Network Considering Signal Distortion[J]. Electric Power Information and Communication Technology, 2024, 22(10): 1-8. DOI: 10.16543/j.2095-641x.electric.power.ict.2024.10.01

考虑信号畸变的多源信息融合配电网故障定位方法

Multi-source Information Fusion Fault Localization Method for Distribution Network Considering Signal Distortion

  • 摘要: 准确定位配电网故障区段,对提升供电服务满意度、优化营商环境具有重要意义。目前基于低压侧用户停电信息的多源信息融合配电网故障定位方法在馈线自动化终端(feeder terminal unit,FTU)信号发生畸变时,依然会出现误判,特别是在低压侧用户停电信息采集失败时,故障定位准确率大大降低。文章在现有模型基础上引入FTU开关跳闸(变位)信号,校正模型输入,构建了一个高容错度的配电网故障定位模型。通过算例仿真分析,证明了该方法在单一故障信号畸变和停电信息采集失败2种场景下相较于未考虑信号校正的方法具有更高的准确性。

     

    Abstract: Accurately locating the fault section of the distribution network can have significant implications for improving power supply service satisfaction and optimizing the business environment.At present, the multi-source information fusion distribution network fault location method based on the low-voltage user outage information will still misjudge when the signal of the automated feeder terminal unit (FTU) is distorted, especially when the low-voltage user outage information collection fails, the fault location accuracy is greatly reduced.This paper introduces a FTU switch trip signal to adjust the model input based on the existing framework, ultimately constructing a fault location model with enhanced fault tolerance.The simulation results show that the proposed method has higher accuracy than the method without signal correction when the single fault signal is distorted or the fault information of low-voltage users cannot be collected.

     

/