刘枫, 李晓方, 秦莉敏, 李俊华, 丁心晓, 郭飞. 针对辐射型电网母联死区故障的保护改进设计[J]. 电力系统自动化, 2013, 37(22): 122-124.
引用本文: 刘枫, 李晓方, 秦莉敏, 李俊华, 丁心晓, 郭飞. 针对辐射型电网母联死区故障的保护改进设计[J]. 电力系统自动化, 2013, 37(22): 122-124.
LIU Feng, LI Xiaofang, QIN Limin, LI Junhua, DING Xinxiao, GUO Fei. Protection Improvement Design for Bus Coupler Dead-zone Fault of Radiation Grid[J]. Automation of Electric Power Systems, 2013, 37(22): 122-124.
Citation: LIU Feng, LI Xiaofang, QIN Limin, LI Junhua, DING Xinxiao, GUO Fei. Protection Improvement Design for Bus Coupler Dead-zone Fault of Radiation Grid[J]. Automation of Electric Power Systems, 2013, 37(22): 122-124.

针对辐射型电网母联死区故障的保护改进设计

Protection Improvement Design for Bus Coupler Dead-zone Fault of Radiation Grid

  • 摘要: 为确保双母线运行方式下,在母联死区范围内发生故障时,变电站不会全站停电,可以保部分负荷运行,文中对现有母差保护和母联死区保护进行分析研究,对现有母线保护设计方案进行了改进,使其在母线故障时能准确切除故障母线,且在母联死区范围内故障时,也能正确切除母联断路器及与故障相关的母线。最后,通过对母联断路器的动作时间测定,说明此方案可行。

     

    Abstract: In order to guarantee that no whole transformer substation power outage will occur but partial load is certain to run when the bus coupler dead-zone goes faulty in the double bus operation mode,the differential protection of both the bus and the bus coupler dead-zone is studied.The existing bus protection scheme is improved so that it will act correctly during bus fault.Even though fault should occur in the bus dead-zone,it can still correctly disconnect the bus coupler breaker and the related bus.Finally,by estimating the action time of the bus coupler breaker,the feasibility of the scheme is proved.

     

/