Harmonic Measurement Error Test Technology of Capacitor Voltage Transformer
-
摘要: 电容式电压互感器(CVT)被广泛应用于高压系统中的电压测量、继电保护及载波通信等场合。文中研究谐波条件下CVT测量误差的试验分析方法。设计了采用试验用小容量升压变压器提供高压谐波源的试验平台,分析了高压侧谐波电压放大和衰减的原因,通过仿真验证了所得结论的正确性。在此基础上提出了将试验升压变压器更换为大容量普通升压变压器的方案,完成了CVT谐波测量误差的试验。建立了CVT的谐波等效电路并分析了谐波条件下其内部电路的谐振模式,通过理论分析和仿真计算对试验平台的有效性和试验结果的正确性进行了验证。Abstract: Capacitor voltage transformer(CVT)is widely used for voltage measurement,relay protection and carrier communications in the high-voltage system.In this paper,the measurement error test method of CVT under the harmonic background is researched.First,a test system using a step-up transformer for testing to provide the high-voltage harmonic source is established.The reasons of harmonic voltage amplification and attenuation on high voltage side are analyzed.On this basis,the reformation project which replaces the experimental step-up transformer with the ordinary step-up transformer is proposed.Then,the harmonic measurement error of CVT is analyzed.The harmonic equivalent circuit of CVT is built and the resonant mode of its internal circuit is analyzed.Through the theoretical analysis and the simulation,the effectiveness of the test platform and the validity of simulation results are verified.
-
[1] 王德忠,王季梅.电容式电压互感器速饱和电抗型阻尼器的研究[J].电工技术学报,2000,15(1):41-46. WANG Dezhong,WANG Jimei.A study of the protective device with inductor in series resistance for capacitor voltage transformer[J].Transactions of China Electrotechnical Society,2000,15(1):41-46.
[2] 熊小伏,周家启,周永忠.基于迭加原理的CVT暂态特性校正新方法[J].电工技术学报,2006,21(8):107-111. XIONG Xiaofu,ZHOU Jiaqi,ZHOU Yongzhong.A new method of correcting transient characteristics of capacitive voltage transformer using principle of superposition[J].Transactions of China Electrotechnical Society,2006,21(8):107-111.
[3] 邬林勇,何正友,钱清泉.利用CVT二次信号的频域行波故障测距方法[J].电力系统自动化,2008,32(8):73-82. WU Linyong,HE Zhengyou,QIAN Qingquan.Frequency domain traveling wave fault location method using CVT’s secondary signals[J].Automation of Electric Power Systems,2008,32(8):73-82.
[4] 许明,高厚磊,邹贵彬.基于积分等值变换的电容式电压互感器暂态误差校正方法[J].电力系统自动化,2011,35(1):71-76. XU Ming,GAO Houlei,ZOU Guibin.An integral equivalent transformation based method for capacitor voltage transformer(CVT)transient error correction[J].Automation of Electric Power Systems,2011,35(1):71-76.
[5] 王德忠,王季梅.电容式电压互感器误差频率特性的研究[J].高电压技术,2001,27(2):66-68. WANG Dezhong,WANG Jimei.The study of error characteristic changing with frequency for capacitor voltage transformer[J].High Voltage Engineering,2001,27(2):66-68.
[6] 孙建涛,文习山,王晓琪.绝缘在线监测中电容式电压互感器的误差校正[J].电力系统自动化,2008,32(16):61-65. SUN Jiantao,WEN Xishan,WANG Xiaoqi.Error correction of capacitor voltage transformers for insulation on-line monitoring[J].Automation of Electric Power Systems,2008,32(16):61-65.
[7] Capacitor voltage transformers:IEC 60044-5—2004[S].2004.
[8] 杨金涛,乐健,汪妮,等.谐波背景下电能计量系统的计算误差分析[J].电力系统自动化,2015,39(13):144-150.DOI: 10.7500/AEPS20140710014. YANG Jintao,LE Jian,WANG Ni,et al.Analysis of measurement error for electric energy metering system under harmonic conditions[J].Automation of Electric Power Systems,2015,39(13):144-150.DOI: 10.7500/AEPS20140710014.
[9] 周存和.关于电容式电压互感器测量谐波电压的问题[J].电力电容器,2006(2):43-45. ZHOU Cunhe.Some problem about harmonic voltage measurement by capacitor voltage transformer[J].Power Capacitor,2006(2):43-45.
[10] XIAO Yao,FU Jun,HU Bin.Problems of voltage transducer in harmonic measurement[J].IEEE Trans on Power Delivery,2004,19(3):1483-1487.
[11] 王锐.CVT谐波测量畸变研究[D].北京:华北电力大学,2008. [12] KOJOVIC L,KEZUNOVIC M,FROMEN C W.A new method for the CCVT performance analysis using filed measurement,signal processing and EMTP modeling[J].IEEE Trans on Power Delivery,1994,9(4):1907-1914.
[13] GHASSEMI F,GALE P F,CLEGG B.Method to measure CVT transfer function[J].IEEE Trans on Power Delivery,2002,17(4):915-920.
[14] 郜洪亮,李琼林,余晓鹏,等.电容式电压互感器的谐波传递特性研究[J].电网技术,2013,37(11):3125-3130. GAO Hongliang,LI Qionglin,YU Xiaopeng,et al.Harmonic transfer characteristic of capacitor voltage transformer[J].Power System Technology,2013,37(11):3125-3130.
计量
- 文章访问数: 0
- HTML全文浏览量: 0
- PDF下载量: 0