Abstract:
Based on virtual fault port method,a formula for calculating the virtual port parameters which considers the line-to-ground capacitance and multi-line mutual inductance is derived.Then it presents the fault voltage and current distribution calculation method considering the transformer phase shifting.On the basis,the fault calculation program is developed and used for relay setting and verification.Test results show that the method has better calculation speed and accuracy,and is very effective for fault calculation.