基于馈线负荷骤降度的配电网故障研判方法
Distribution network fault location method based on the sudden drop ratio of feeder active load
-
摘要: 针对自动化水平低的配电线路故障停电后难以准确快速定位故障区段和停电范围的问题,提出了一种基于馈线负荷骤降度的配电网故障研判方法。该方法在馈线首端有功功率的骤降度大于一定阈值时启动,然后利用计量自动化系统中配变的历史负荷数据预测故障前馈线上各配变的有功功率,并计算馈线上各开关的负荷占比。通过比较馈线负荷骤降度与各开关负荷占比值,判断故障跳闸开关及停电范围。工程实例的分析结果表明,该方法能够准确定位故障跳闸开关,实时性好,为配电网提供了一种不依赖配电网自动化系统的新的故障研判手段。Abstract: It is difficult to accurately and quickly locate the fault section and outage range after power failure in a distribution network with low-level automation. To solve this problem, a fault location and diagnosis method based on sudden drop ratio(SDR) of the feeder active load is proposed. After the feeder SDR exceeds a certain threshold, the active power of each distribution transformer on the faulty feeder is predicted using the historical load data in the metering automation system, and the load proportion of each switch is calculated. By comparing the feeder SDR and the power proportion of each switch, the fault trip switch and power failure range are judged. Analysis of the results of an engineering example show that the method can accurately locate the fault trip switch, and has good real-time performance.It provides a new fault diagnosis technique for a distribution network independent of the distribution network automation system.