330 kV变电站隔离开关触头腐蚀失效分析
Analysis on Corrosion Failures of Disconnector Contact in a 330 kV Substation
-
摘要: 针对330 kV变电站隔离开关触头腐蚀事件,通过采用宏观检查、材质分析、扫描电镜微观形貌及元素面扫描等试验手段开展了腐蚀机理分析,查找出隔离开关腐蚀失效的真实原因,并提出了防范措施。Abstract: In allusion to a contact corrosion event of disconnector in 330 kV substation, the corrosion mechanism is analyzed by means of macro inspection, material analysis, scanning electron microscope micro morphology and element surface scanning, etc., the real cause of corrosion failure of disconnector is found out,and preventive measures are put forward.