水电站消防供水管路波动分析及处理
Analysis and Treatment of Fluctuations of Firefighting Water Supply Pipeline of Hydropower Station
-
摘要: 对水电站消防供水系统所存在波动造成管路阀门破裂原因进行分析查找,并提出解决的思路和改进方案,对原来不合理的设计通过合理配置减压阀、补气排气阀等方法进行改造,并对消防管路改造工期安排及施工安全措施进行了详细论述。Abstract: This article mainly analyzes and investigates into the causes of valve rupture caused by the fluctuations in firefighting water supply pipeline system of hydropower stations, and proposes an idea for improvement solution, puts forward the rational configuration of pressure relief valves and supplemental gas exhaust valves to modify the original inappropriate design, and discusses in detail the schedule and safety measures for the retrofit of the firefighting water pipeline.