Abstract:
The trip accident of main transformer in wind farm is analyzed. According to the current transformer winding distribution,combined with the result of double relay protective device operation inconsistency,the location of locked fault points between two sets of protection windings in current transformer is analyzed. Combined with eighteen countermeasures and standardized design specifications,the rectification suggestions for transformer winding distribution are put forward,which can provide a reference for subsequent projects.