一起10 kV II段母线失压故障分析

Analysis of a 10 kV II Section Bus Voltage Loss Fault

  • 摘要: 雷雨天气造成变电站10 kV II段TV三相一次保熔断,满足10 kV备自投装置检无压条件,由于10 kV II母所带负载过小,且在10 kV 59019线跳闸且重合之后,部分负荷暂时未能启动恢复,导致II母A相二次电流为减小至0.06 A,满足10 kV备自投II母检无流的条件,10 kV备自投启动,延时跳开5902开关,由于备自投合母联开关硬压板未在合闸投用状态,造成合母联开关失败,10 kV II母电源未能得到恢复。

     

/