赵俊, 高会芳, 徐大鹏, 陈波, 刘轩, 王磊. 110 kV OPGW光缆U型构件过热故障分析[J]. 农村电气化, 2020, (7): 39-41. DOI: 10.13882/j.cnki.ncdqh.2020.07.012
引用本文: 赵俊, 高会芳, 徐大鹏, 陈波, 刘轩, 王磊. 110 kV OPGW光缆U型构件过热故障分析[J]. 农村电气化, 2020, (7): 39-41. DOI: 10.13882/j.cnki.ncdqh.2020.07.012
Zhao Jun, Gao Huifang, Xu Dapeng, Chen Bo, Liu Xuan, Wang Lei. Overheating Fault Analysis of U Type Structural Member of 110 kV OPGW Optical Cable[J]. Rural Electrification, 2020, (7): 39-41. DOI: 10.13882/j.cnki.ncdqh.2020.07.012
Citation: Zhao Jun, Gao Huifang, Xu Dapeng, Chen Bo, Liu Xuan, Wang Lei. Overheating Fault Analysis of U Type Structural Member of 110 kV OPGW Optical Cable[J]. Rural Electrification, 2020, (7): 39-41. DOI: 10.13882/j.cnki.ncdqh.2020.07.012

110 kV OPGW光缆U型构件过热故障分析

Overheating Fault Analysis of U Type Structural Member of 110 kV OPGW Optical Cable

  • 摘要: 光纤复合架空地线(OPGW)光缆U型构件过热,破坏其外部铝合金构件,严重影响光缆的正常通信功能。结合故障时运维人员巡检情况,利用红外检测技术、接地电流测试等手段,认为OPGW光缆U型构件过热的直接原因是OPGW光缆接地引下线设计不规范。OPGW光缆和门型架构通过U型构件直接连接,没有专用的接地引下线,架空地线的感应电流持续放电灼伤U型构件,致使过热。而导致故障的主要原因是110 kV升压站外输电线路杆塔接地电阻过大,致使U型构件发热过高。结合故障原因,并且提出相应的建议及整改措施。

     

/

返回文章
返回