一起电压切换功能缺陷案例的分析

An analysis of a voltage switching function defect case

  • 摘要: 本文就一起因为刀闸辅助触点接反从而导致电压切换装置不能正常进行电压切换的事件案例,利用不同运行方式下刀闸触点的状态真值表结合装置所发出的信号以及接点电位,对缺陷原因进行分析和验证,并说明该缺陷的隐蔽性。文章简述了缺陷的查找过程以及规避风险的措施,最后给出了缺陷的处理方案。

     

    Abstract: Focusing on a event that the voltage switching device had incorrect operation caused by the inverse connection of the auxiliary contact of the disconnector.Conbined with the state table of auxiliary contacts under different operation mode, the signals from the device and the node poten- tial ,this essay carries out a defect analysis on the signal in terms of normal connection and incor- rect connection.Ultimately ,it verifies the concealment of the defect and portraies the process of solving problem and the measures to evade processing risks.

     

/

返回文章
返回