Abstract:
Most large transformers adopt forced oil circulation directed air cooling (ODAF) cooling mode. In order to enhance the reliability of cooling system and improve the safe operation performance of transformers, the design scheme of grouping and automatic control of multi-group coolers is often adopted. Due to the wide application of grouping scheme and the introduction of PLC controller, and after years of use, the cooler control system gradually tends to be perfect, but there are also some problems ignored. This paper first describes the main transformer PLC air cooling control system of a substation and its basic working principle of each component module, and then the main transformer put into operation when the cooler stop tripping reasons are analyzed, find outTypical problems existing in the loop of main transformer air cooling control system are presented.