Abstract:
During the fixed inspection of the main transformer protection device and the inspection of the secondary circuit, it was found that the neutral wire of the secondary circuit of the differential current of the main transformer was miswired, and there was a major hidden danger of misoperation of the main transformer differential protection, which was eliminated by taking limited measures. Normative inspection of the current secondary circuit is an important inspection item for relay protection workers when the protection equipment is overhauled, newly installed or the current transformer circuit changes greatly. To eliminate the hidden trouble of protection misoperation caused by the wrong wiring of the secondary current circuit, finally, it summarizes and puts forward the working norms that relay protection workers need to abide by in operation and maintenance and the specific measures to prevent this similar incident.