110kV变压器绕组变型测试试验分析

Test Analysis of 110kV Transformer Winding Deformation

  • 摘要: 电力变压器的正常运行关乎整个系统的安全稳定,在长期运行条件下,绕组变形是变压器故障的常见类型。本文主要针对昭通供电局110kV凤凰变#2主变进行绕组变形试验测试,对短路阻抗法、频率响应法和震荡波法实验数据分析,检验变压器绕组的变形状况,证明震荡波法在变压器绕组变型测试中具有相当的可靠性。

     

    Abstract: The normal operation of power transformer is related to the safety and stability of the whole system. Under the long-term operation condition, winding deformation is a common type of transformer faults. This paper mainly tests the winding deformation of # 2 main transformer of 110kV Fenghuang substation in Zhaotong Power Supply Bureau,.It analyzes the experimental data of short-circuit impedance method, frequency response method and shock wave method, tests the deformation of transformer winding, and proves the shock wave method is considerable reliable in the transformer winding deformation test.

     

/