一起35kV变电站站用变高压侧保险故障导致电网异常事件分析

Analysis of an abnormal power grid event caused by a high voltage side insurance fault of 35kV substation transformer

  • 摘要: 摘要:电力系统中,由于局部地区电网电源点单一,况且小电源上网运行,保护装置功能配置不完全适用,造成线路保护重合闸装置无法正常动作。本文结合生产实际,分析了一起35kV变电站站用变高压侧保险短路故障,35kV线路保护重合闸动作不成功事件,并结合事件原因提出了装置功能配置的整改建议,及采取防雷措施,提高局部电网的安全稳定运行。

     

    Abstract: ABSTRACT: In the power system, due to the single power supply point of the local power grid, and the small power supply running on the grid, it is difficult to coordinate the setting of relay protection, resulting in the failure of the line protection reclosing device to operate normally. Combined with the production practice, this paper analyzes a high-voltage side insurance fault of 35kV substation transformer and the unsuccessful action of 35kV line protection reclosing, and puts forward the rectification suggestions of protection setting and device function configuration, and takes lightning protection measures to improve the safe and stable operation of local power grid.

     

/