湿式电除尘器跳闸原因分析及处理方法

ENGLISH TCAUSE ANALYSIS AND TREATMENT OF WET ELECTROSTATIC PRECIPITATOR TRIP

  • 摘要: 摘要:某某热电厂2*350MW机组#1、2炉湿除电场自投运以来,发生多次因湿除加热风机及加热器跳闸引起湿除电场误跳闸事故,造成环保指标超标,引起重大经济损失。对湿除加热风机控制回路进行了理论分析,指出了存在的问题并提出了解决方法。

     

    Abstract: ABSTRACT: Since the wet dewatering electric field of 2*350MW unit #1 and 2 furnace in xx thermal power plant has been put into operation, the wet dewatering electric field mistrip accidents have occurred for many times due to the trip of the wet dewatering heating fan and heater, resulting in the environmental protection index exceeding the standard and causing significant economic losses. In this paper, the control circuit of wet dewatering heating fan is analyzed theoretically, the existing problems are pointed out and the solutions are put forward.

     

/