考虑桩-土-上部结构相互作用的输电塔抗震性能研究

Seismic Performance Research of Transmission Tower In Consideration of The Pile-soil-structure System

  • 摘要: 本文以某一实际220kV输电线路工程为依托,在地震作用下,对桩-土-结构相互作用下输电塔的抗震性能进行研究。利用有限元软件ABAQUS,分别建立输电塔模型和桩-土-输电塔的整体模型。首先,采用时程分析的方法计算桩-土-输电塔体系在地震作用下的动力响应,其中土体根据实际情况分为四类情况。其次,计算刚性地基情况在地震作用下的动力响应。最后,通过两种不同模型的计算结果分析得出如下结论:考虑桩-土-结构相互作用后,结构的自振周期较原来变长。其中在软土和中软土场地,与不考虑相互作用的动力响应差异较大,塔顶位移极大值相对增量分别为39.82%和21.88%。建议在中软土和软土场地条件下对输电塔进行抗震设计时,应对桩-土-上部结构相互作用的影响给予充分的考虑。

     

    Abstract: This paper studied the seismic behavior of the transmission tower under the action of earthquake, Which is based on a project of an actual 220kV transmission line. The transmission tower model and the whole model of the pile-soil- transmission tower system are established respectively by using the finite element software ABAQSU. First, the time history analysis method is used to calculate the dynamic response of the pile-soil-transmission tower system under earthquake load, and the soil is divided into four kinds according to the actual situation. Secondly, the dynamic response of rigid foundation under seismic load is calculated. Finally, the following conclusions are obtained from the analysis of the two different models: After considering the interaction of the system, the period of the structure have extended and the mode of the structure lagged. On soft sites and medium soft sites, compare with no considering the interaction, the results have a big difference, the relative increment of the maximum displacement at the top of the tower is 39.82% and 21.88%,respectively. Therefore it is suggested that the pile-soil-structure dynamic interaction should be fully considered in aseismic design of transmission tower on soft sites and medium soft sites.

     

/

返回文章
返回