风电场箱变低压电缆同相多根并联运行温度异常分析与处理

Analysis and treatment of temperature anomaly in parallel operation of multiple parallel low-voltage cable with box transformer in wind farm

  • 摘要: 为了提高电缆的输电能力及方便施工,风电场箱变低压侧地埋电缆每相采用多根单芯电缆并联接线,因设计及现场电缆敷设施工不规范,造成同相每根电缆互感电抗不同,电流不均衡,导致部分电缆过温,可能发生电缆击穿故障。本文通过分析查找箱变低压侧电缆过热原因,采取合理分配电缆方案,保证了各电缆电流基本平衡,彻底解决了电缆高温问题,为同类型缺陷提供了参考作用。

     

    Abstract: In order to improve the transmission capacity of the cable and facilitate the construction, multiple single-core cables are connected in parallel for each phase of the buried cable on the low-voltage side of the box-type transformer in the wind farm. Due to the non-standard design and on-site cable laying construction, the mutual inductance reactance of each cable in the same phase is different, and the current is unbalanced, resulting in over-temperature of some cables and possible cable breakdown.In this paper, the reasons for cable overheating on the low voltage side of the transformer box are analyzed, and a reasonable cable distribution scheme is adopted to ensure the basic balance of the current of each cable, completely solve the problem of cable high temperature, and provide a reference for similar defects.

     

/