一起典型馈供线路的断线故障导致主变保护动作情况分析

Analysis of the Main Transformer Protection Action Caused by a Typical Feeder Line Breakage Fault

  • 摘要: 本文通过基于正序、负序、零序分量的复合序网分析方法对馈供线路发生单相断线故障进行分析,理论分析结果表明断线相的电压与断口两侧主变中性点是否接地密切相关,若馈供线路主变中性点不接地时,会导致母线开口零序电压升高,进而导致主变保护零序过压动作;本文根据故障时电气量特征和实际故障波形分析保护动作行为,指出现有变电站内继电保护逻辑对单相断线故障时处理存在的不足,提出改进方案来提高供电的可靠性

     

    Abstract: This article uses a composite sequence network analysis method based on positive sequence, negative sequence, and zero sequence components to analyze single-phase disconnection faults in feeder lines. The theoretical analysis results show that the voltage of the disconnection phase is closely related to whether the neutral points of the main transformer on both sides of the disconnection are grounded. If the neutral points of the main transformer on the feeder line are not grounded, it will lead to an increase in the zero sequence voltage of the busbar opening, which in turn will cause the zero sequence overvoltage action of the main transformer protection; This article analyzes the protection action behavior based on the electrical characteristics during faults and the actual fault waveform. It points out the shortcomings of relay protection logic in substations in dealing with single-phase disconnection faults, and proposes improvement plans to improve the reliability of power supply

     

/

返回文章
返回