一起火电厂DCS系统操作员站全部离线 异常事件原因分析

Cause analysis of an abnormal event that DCS system operator station were all offline in thermal power plant

  • 摘要: 针对华能靖远热电有限公司#1机组DCS系统操作员站全部离线的异常事件,热控检修人员分别对DCS系统上位机、控制器、交换机的历史记录信息、日志等进行分析判断,最终确定交换机的组播转发功能的开启导致该不安全事件的发生,并提供相应的解决措施。

     

    Abstract: In view of the abnormal event that all the operator stations of DCS system in Unit #1 of Huaneng Jingyuan Thermal Power Co., LTD.were offline, thermal control maintenance personnels analyzed the historical record information and logs of the host computer, controller and switch of DCS system respectively, and finally determined that the multicast forwarding function of the switch led to the occurrence of the unsafe event, and provided corresponding solutions.

     

/

返回文章
返回