关于550PM63-40型断路器三相不一致保护引起误动的整改分析

Rectification analysis of malfunction caused by three-phase inconsistent protection of 550PM63-40 circuit breaker

  • 摘要: 在220kV及以上的高电压等级电网中系统发生非全相运行的情况,会造成设备损坏、冲击电网,存在安全隐患、能源浪费等各种危害。本文通过对北京ABB高压开关设备有限公司的550PM63-40型断路器三相不一致保护可能造成误动的隐患整改,从非全相运行的危害、针对550PM63-40型断路器三相不一致保护接线的专项整改措施以及对整改效果的验收进行分析。

     

    Abstract: In the high-voltage power grid of 220kV and above, the system will run out of phase,  which will cause equipment damage and impact the power grid, and there will be various  hazards such as security risks and energy waste. In this paper, the hidden dangers of malfunction caused by the three-phase inconsistent protection of 550PM63-40 circuit breaker in Beijing ABB High Voltage switch equipment Co.Ltd. are rectified, and the hazards of non-full-phase  operation, the special rectification measures for the three-phase inconsistent protection wiring of 550PM63-40 circuit breaker and the acceptance of the rectification effect are analyzed.

     

/