一起线路发生故障其两侧保护装置动作行为不一致案列分析研究

Analysis and research on the inconsistent action behavior of the protection de-vices on both sides of the line fault

  • 摘要: 本文详细论述了线路发生故障两侧保护装置保护行为不一致的分析,线路发生故障时一侧保护装置动作而另一侧保护装置只有保护启动。本文从运行情况、故障描述、保护动作报告、录波分析、逻辑推理等分析,结合现场巡视检查,发现了两侧保护装置动作行为不一致的原因,为供电企业处理类似事件提供借鉴和指导,并提出了保护装置可行性的缺陷预防措施,保证电网安全可靠运行。

     

    Abstract: This paper discusses in detail the analysis of the inconsistent protection behavior of protection devices on both sides of the line fault. When the line fault occurs, one side of the protection device acts while the other side of the protection device only starts protection. This article from the run situation, the fault description, protection action report, wave record analysis, logic analysis, combined with field patrol inspection, found on both sides of the protection actions inconsistent reason, to provide reference and guidance for similar power supply enterprises processing, and put forward the feasibility of protection device defects prevention measures, to ensure safe and reliable operation of power grid.

     

/